IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 120VAC 50/60Hz coil, open

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D65AG7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • [Icw] Rated Short-Time Withstand Current
    520 A 104 °F (40 °C) - 10 s power circuit 900 A 104 °F (40 °C) - 1 s power circuit 110 A 104 °F (40 °C) - 10 min power circuit 260 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling cir
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • [Ui] Rated Insulation Voltage
    Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1
  • Motor Power HP (UL / CSA)
    40 hp 460/480 V at AC 50/60 Hz for 3 phase 5 hp 115 V at AC 50/60 Hz for 1 phase 10 hp 230/240 V at AC 50/60 Hz for 1 phase 20 hp 200/208 V at AC 50/60 Hz for 3 phase 20 hp 230/240 V at AC 50/60 Hz for 3 phase 50 hp 575/600 V at A
  • Motor Power Kw
    11 kW 400 V AC 50/60 Hz AC-4) 18.5 kW 220...230 V AC 50/60 Hz AC-3) 30 kW 380...400 V AC 50/60 Hz AC-3) 37 kW 500 V AC 50/60 Hz AC-3) 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Product Certifications
    GOST UL CSA CCC
  • Control Circuit Voltage Limits
    0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 60 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 60 Hz
  • Connections - Terminals
    Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)fle
  • Tightening Torque
    Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagon
  • Utilisation Category
    AC-4 AC-3 AC-1
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 125 A gG <= 690 V type 1 power circuit 125 A gG <= 690 V type 2 power circuit
  • Irms Rated Making Capacity
    140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 1000 A 440 V power circuit IEC 60947
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Mounting Support
    Rail Plate
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Power Dissipation Per Pole
    9.6 W AC-1 6.3 W AC-3
  • Electrical Durability
    1.4 Mcycles 80 A AC-1 <= 440 V 1.45 Mcycles 65 A AC-3 <= 440 V
  • [Ue] Rated Operational Voltage
    Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current
    10 A 140 °F (60 °C) signalling circuit 80 A 140 °F (60 °C) power circuit
  • [Ie] Rated Operational Current
    80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 65 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
  • Operating Time
    4...19 ms opening 12...26 ms closing
  • Contactor Application
    Motor control Resistive load
  • Hold-In Power Consumption In VA
    13 VA 60 Hz 0.3 68 °F (20 °C))
  • Signalling Circuit Frequency
    25...400 Hz
  • Coil Technology
    Without built-in suppressor module
  • Mechanical Durability
    6 Mcycles
  • Insulation Resistance
    > 10 MOhm signalling circuit
  • Minimum Switching Voltage
    17 V signalling circuit
  • Minimum Switching Current
    5 mA signalling circuit
  • Heat Dissipation
    4…5 W 60 Hz
  • Inrush Power In VA
    140 VA 60 Hz 0.75 68 °F (20 °C))
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Average Impedance
    1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Rated Breaking Capacity
    1000 A 440 V power circuit IEC 60947
  • Front Cover
    With
  • Overvoltage Category
    III
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • [Uc] Control Circuit Voltage
    120 V AC 60 Hz
  • Control Circuit Type
    AC 60 Hz
  • Device Short Name
    LC1D
  • Power Pole Contact Composition
    3 NO
  • Product Name
    TeSys D
  • Product Or Component Type
    Contactor
  • Poles Description
    3P
  • Range
    TeSys

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



This item can ship within 24h!

Manufacturer warranty

$435.68

Stock:

5

Select Qty:

$435.68

$435.68 each

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

Relevant products

What can I help you find today?

Recommended parts