LC1D256BL Schneider Electric Industrial Automation Components

LC1D256BL on Powermatic Associates
Schneider Electric

Part#:LC1D256BL

Manufacturer:Schneider Electric

Product Lifecycle:Active

In-stock parts: 19

Nov 16, 2024

IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24VDC coil, open style

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1D256BL Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    GL CSA GOST RINA LROS (Lloyds register of shipping) DNV BV CCC UL
  • [Icw] Rated Short-Time Withstand Current
    240 A 104 °F (40 °C) - 10 s power circuit 380 A 104 °F (40 °C) - 1 s power circuit 50 A 104 °F (40 °C) - 10 min power circuit 120 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circ
  • Motor Power HP (UL / CSA)
    3 hp 230/240 V at AC 50/60 Hz for 1 phase 2 hp 115 V at AC 50/60 Hz for 1 phase 7.5 hp 230/240 V at AC 50/60 Hz for 3 phase 15 hp 460/480 V at AC 50/60 Hz for 3 phase 20 hp 575/600 V at AC 50/60 Hz for 3 phase 7.5 hp 200/208 V at
  • Motor Power Kw
    5.5 kW 220...230 V AC 50/60 Hz AC-3) 11 kW 380...400 V AC 50/60 Hz AC-3) 11 kW 415...440 V AC 50/60 Hz AC-3) 15 kW 500 V AC 50/60 Hz AC-3) 15 kW 660...690 V AC 50/60 Hz AC-3) 5.5 kW 400 V AC 50/60 Hz AC-4)
  • [Ui] Rated Insulation Voltage
    Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • Tightening Torque
    Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 22.13 lbf.in (2.5 N.m) lugs-ring terminals flat Ø 8 mm M4 Power circuit 2
  • Control Circuit Voltage Limits
    0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.8...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 63 A gG <= 690 V type 1 power circuit 40 A gG <= 690 V type 2 power circuit
  • Utilisation Category
    AC-1 AC-3 AC-4
  • Irms Rated Making Capacity
    140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 450 A 440 V power circuit IEC 60947
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • Connections - Terminals
    Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.39 in (10 mm))
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Power Dissipation Per Pole
    3.2 W AC-1 1.25 W AC-3
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Contactor Application
    Motor control Resistive load
  • [Ie] Rated Operational Current
    25 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 40 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
  • Electrical Durability
    1.65 Mcycles 25 A AC-3 <= 440 V 1.4 Mcycles 40 A AC-1 <= 440 V
  • [Ith] Conventional Free Air Thermal Current
    10 A 140 °F (60 °C) signalling circuit 40 A 140 °F (60 °C) power circuit
  • Mounting Support
    Rail Plate
  • [Ue] Rated Operational Voltage
    Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • Operating Time
    65.45...88.55 ms closing 20...30 ms opening
  • Insulation Resistance
    > 10 MOhm signalling circuit
  • Minimum Switching Current
    5 mA signalling circuit
  • Hold-In Power Consumption In W
    2.4 W 68 °F (20 °C)
  • Coil Technology
    Built-in bidirectional peak limiting diode suppressor
  • Time Constant
    40 ms
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Minimum Switching Voltage
    17 V signalling circuit
  • Signalling Circuit Frequency
    25...400 Hz
  • Inrush Power In W
    2.4 W 68 °F (20 °C))
  • Mechanical Durability
    30 Mcycles
  • Front Cover
    With
  • Average Impedance
    2 mOhm - Ith 40 A 50 Hz power circuit
  • Rated Breaking Capacity
    450 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • Overvoltage Category
    III
  • [Uc] Control Circuit Voltage
    24 V DC
  • Control Circuit Type
    DC low consumption
  • Device Short Name
    LC1D
  • Poles Description
    3P
  • Range
    TeSys
  • Product Name
    TeSys D
  • Product Or Component Type
    Contactor
  • Power Pole Contact Composition
    3 NO

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



This item can ship within 24h!

Manufacturer warranty