LC1D186BD Schneider Electric Industrial Automation Components
Part#:LC1D186BD
Manufacturer:Schneider Electric
Product Lifecycle:Active
In-stock parts: 25
Oct 26, 2024
IEC contactor, TeSys Deca, nonreversing, 18A, 10HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style
About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.
Check out the LC1D186BD Schneider Electric price in the box on the right side or send a quick quote.
Product Details
- Product Certifications LROS (Lloyds register of shipping) RINA DNV GOST BV CSA CCC GL UL
- [Ui] Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
- Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
- Motor Power HP (UL / CSA) 1 hp 115 V at AC 50/60 Hz for 1 phase 3 hp 230/240 V at AC 50/60 Hz for 1 phase 5 hp 200/208 V at AC 50/60 Hz for 3 phase 5 hp 230/240 V at AC 50/60 Hz for 3 phase 10 hp 460/480 V at AC 50/60 Hz for 3 phase 15 hp 575/600 V at AC 5
- [Icw] Rated Short-Time Withstand Current 145 A 104 °F (40 °C) - 10 s power circuit 240 A 104 °F (40 °C) - 1 s power circuit 40 A 104 °F (40 °C) - 10 min power circuit 84 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circu
- Motor Power Kw 4 kW 220...230 V AC 50/60 Hz AC-3) 7.5 kW 380...400 V AC 50/60 Hz AC-3) 9 kW 415...440 V AC 50/60 Hz AC-3) 10 kW 500 V AC 50/60 Hz AC-3) 10 kW 660...690 V AC 50/60 Hz AC-3) 4 kW 400 V AC 50/60 Hz AC-4)
- Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 8 mm M3.5 Power circuit
- Control Circuit Voltage Limits 0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC 0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
- Irms Rated Making Capacity 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 300 A 440 V power circuit IEC 60947
- Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 50 A gG <= 690 V type 1 power circuit 35 A gG <= 690 V type 2 power circuit
- Utilisation Category AC-1 AC-4 AC-3
- Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
- Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
- Operating Time 53.55...72.45 ms closing 16...24 ms opening
- Electrical Durability 1.65 Mcycles 18 A AC-3 <= 440 V 1 Mcycles 32 A AC-1 <= 440 V
- Contactor Application Motor control Resistive load
- Mounting Support Plate Rail
- Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Ith] Conventional Free Air Thermal Current 10 A 140 °F (60 °C) signalling circuit 32 A 140 °F (60 °C) power circuit
- [Ie] Rated Operational Current 18 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 32 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
- Power Dissipation Per Pole 2.5 W AC-1 0.8 W AC-3
- Connections - Terminals Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.31 in (8 mm))
- [Ue] Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
- Minimum Switching Voltage 17 V signalling circuit
- Insulation Resistance > 10 MOhm signalling circuit
- Minimum Switching Current 5 mA signalling circuit
- Signalling Circuit Frequency 25...400 Hz
- Inrush Power In W 5.4 W 68 °F (20 °C))
- Coil Technology With integral suppression device
- Hold-In Power Consumption In W 5.4 W 68 °F (20 °C)
- Time Constant 28 ms
- Maximum Operating Rate 3600 cyc/h 140 °F (60 °C)
- Mechanical Durability 30 Mcycles
- Front Cover With
- Rated Breaking Capacity 300 A 440 V power circuit IEC 60947
- Average Impedance 2.5 mOhm - Ith 32 A 50 Hz power circuit
- Auxiliary Contact Composition 1 NO + 1 NC
- Overvoltage Category III
- [Uc] Control Circuit Voltage 24 V DC
- Control Circuit Type DC standard
- [Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
- Power Pole Contact Composition 3 NO
- Device Short Name LC1D
- Product Or Component Type Contactor
- Poles Description 3P
- Range TeSys
- Product Name TeSys D
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Related documents LC1D186BD Specs
This item can ship within 24h!
Manufacturer warranty
$170.00
Stock:
25
Select Qty:
$170.00
$170.00 each
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
Relevant products
What can I help you find today?