HDL26070 Schneider Electric Industrial Automation Components


Part#:HDL26070
Manufacturer:Schneider Electric
Category:Industrial Automation Components
Product Lifecycle:Active
Product description
Square D by Schneider Electric HDL26070 is a Moulded Case Circuit Breaker (MCCB) within the PowerPacT HDL sub-range, designed with a PowerPact H-Frame 150 TMD 2P 70A 600Vac/250Vdc 14kA with lugs at 80% rated for both load and line sides. This 2-pole (2P) circuit breaker features thermal protection for overload scenarios and magnetic protection for short-circuit conditions. It has a rated current of 70A, with a rated insulation voltage (Ui) of 750 V, and operates at a rated voltage (AC) of 600Vac 600Y/347Vac. The device is designed for individual unit mount on plate, with a net height of 163 mm, a net width of 104 mm, and a net depth of 86 mm. It offers a degree of protection of IP40 and operates manually via a toggle. The protection settings include over-current fixed at 70A, short-circuit hold current fixed at 800A, and short-circuit trip current fixed at 1450A. The rated operating voltage (Ue) is 690 V, with a rated impulse voltage (Uimp) of 8 kV. The trip current rating is 70 AT, with a frame current rating of 150 AF. Its short circuit breaking rating varies with voltage, including 25kA at 240Vac, 18kA at 480Vac and 480Y/277Vac, 14kA at 600Vac and 600Y/347Vac, and 20kA at 250Vdc, all under UL489. The trip unit type is thermal-magnetic (fixed) without a display, and it falls under utilisation category A.
Product Details
- Electrical Connection Lugs load Lugs line
- Continuous Current Rating 80 %
- Depth 4.36 in (110.74 mm)
- Width 2.74 in (69.60 mm)
- Height 6.4 in (162.56 mm)
- Tightening Torque 44.25 lbf.in (5 N.m) 0.00…0.15 in² (2.5…95 mm²) (AWG 14...AWG 3/0)
- Line Rated Current 70 A
- Magnetic Hold Current 800 A
- Magnetic Tripping Current 1450 A
- Mounting Mode Unit mount
- Product Or Component Type Circuit breaker
- Breaking Capacity Code D
- Number Of Poles 2P
- Range Of Product PowerPact H
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
The price of HDL26070 on Powermatic Associates is $1,062.00. Order now.
HDL26070 Related Documents
Similar products from: Schneider Electric Industrial Automation Components
Manufacturer warranty
HDL26070 Schneider Electric
$1,062.00
Your price can be lower.
Log in or Create account to check your discount
Select Qty:
$1,062.00
$1,062.00 each
Average response time: 11 minutes
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
Compare HDL26070 with other Industrial Automation Components products
Electrical Connection
Continuous Current Rating
Depth
Width
Height
Tightening Torque
Line Rated Current
Magnetic Hold Current
Magnetic Tripping Current
Mounting Mode
Selected product

HDL26070
Schneider Electric
Square D by Schneider Electric HDL26070 is a Moulded Case Circuit Breaker (MCCB) within the PowerPac...
Electrical ConnectionLugs load Lugs line
Continuous Current Rating80 %
Depth4.36 in (110.74 mm)
Width2.74 in (69.60 mm)
Height6.4 in (162.56 mm)
Tightening Torque44.25 lbf.in (5 N.m) 0.00…0....
Line Rated Current70 A
Magnetic Hold Current800 A
Magnetic Tripping Current1450 A
Mounting ModeUnit mount
About the manufacturer
Powermatic Associates is an authorized Schneider Electric distributor, proudly offering a diverse portfolio of innovative solutions tailored to meet the dynamic needs of today's industrial landscape. Schneider Electric stands as a global leader in energy management and automation, providing cutting-edge products and services that drive efficiency and sustainability across a variety of sectors. The...
Recently viewed products
Relevant products
FAQ
What is the price of HDL26070?
Purchase the HDL26070 from Powermatic Associates at the price of $1,062.00. Order today.
Out if stock but available for backorder.
Square D by Schneider Electric HDL26070 is a Moulded Case Circuit Breaker (MCCB) within the PowerPacT HDL sub-range, designed with a PowerPact H-Frame 150 TMD 2P 70A 600Vac/250Vdc 14kA with lugs at 80% rated for both load and line sides. This 2-pole (2P) circuit breaker features thermal protection for overload scenarios and magnetic protection for short-circuit conditions. It has a rated current of 70A, with a rated insulation voltage (Ui) of 750 V, and operates at a rated voltage (AC) of 600Vac 600Y/347Vac. The device is designed for individual unit mount on plate, with a net height of 163 mm, a net width of 104 mm, and a net depth of 86 mm. It offers a degree of protection of IP40 and operates manually via a toggle. The protection settings include over-current fixed at 70A, short-circuit hold current fixed at 800A, and short-circuit trip current fixed at 1450A. The rated operating voltage (Ue) is 690 V, with a rated impulse voltage (Uimp) of 8 kV. The trip current rating is 70 AT, with a frame current rating of 150 AF. Its short circuit breaking rating varies with voltage, including 25kA at 240Vac, 18kA at 480Vac and 480Y/277Vac, 14kA at 600Vac and 600Y/347Vac, and 20kA at 250Vdc, all under UL489. The trip unit type is thermal-magnetic (fixed) without a display, and it falls under utilisation category A.
Similar products from: Industrial Automation Components
What can I help you find today?