2866721 Phoenix Contact AC/DC Power Supplies

Phoenix Contact 2866721 Primary-switched power supply unit, QUINT POWER, Screw connection, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 12 V DC / 20 A
Phoenix Contact

Part#:2866721

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 7

Sep 28, 2024

Primary-switched power supply unit, QUINT POWER, Screw connection, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 12 V DC / 20 A

About the manufacturer: Phoenix Contact is one of the manufacturers that offers AC/DC Power Supplies that you can order at Powermatic Associates site. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 2866721 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Height
    130 mm
  • Width
    90 mm
  • Depth
    125 mm
  • Height with alternative assembly
    130 mm
  • Depth with alternative assembly
    93 mm
  • Degree of protection
    IP20
  • Connection in series
    yes
  • Feedback voltage resistance
    max. 25 V DC
  • Output power
    240 W
  • Typical response time
    < 1 s
  • Maximum power dissipation in no-load condition
    6 W
  • MTBF (IEC 61709, SN 29500)
    > 1000000 h (25 °C)
  • Insulation voltage input/output
    4 kV AC (type test)
  • Insulation voltage input / PE
    3.5 kV AC (type test)
  • Assembly instructions
    alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
  • Connection method
    Screw connection
  • Conductor cross section solid max.
    6 mm²
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section AWG min.
    18
  • EMC requirements for noise immunity
    EN 61000-6-1
  • EMC requirements for noise emission
    EN 61000-6-3
  • Standard - Electrical safety
    IEC 60950-1/VDE 0805 (SELV)
  • Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
    EN 50178
  • Standard – Limitation of mains harmonic currents
    EN 61000-3-2
  • Standard - Approval for medical use
    IEC 60601-1, 2 x MOOP
  • UL approvals
    UL Listed UL 508
  • CSA
    CAN/CSA-C22.2 No. 60950-1-07
  • Electrostatic discharge
    EN 61000-4-2
  • Electromagnetic HF field
    EN 61000-4-3
  • Frequency range
    0.15 MHz ... 80 MHz
  • Test field strength
    10 V/m (Test Level 3)
  • Output
    1 kV (Test Level 2 - symmetrical)
  • Signal
    1 kV (Test Level 2 - asymmetrical)
  • Surge voltage load (surge)
    EN 61000-4-5
  • I/O/S
    asymmetrical
  • Criterion A
    Normal operating behavior within the specified limits.
  • China RoHS
    Environmentally Friendly Use Period = 25;
  • ECLASS 11.0
    27040701
  • ECLASS 5.0
    27242200
  • ECLASS 5.1
    27242200
  • ECLASS 7.0
    27049002
  • ETIM 3.0
    EC001039
  • ETIM 6.0
    EC002540
  • ETIM 7.0
    EC002540
  • UNSPSC 6.01
    30211502
  • UNSPSC 13.2
    39121004
  • Width with alternative assembly
    122 mm
  • Installation distance right/left
    5 mm / 5 mm
  • Installation distance top/bottom
    50 mm / 50 mm
  • Ambient temperature (operation)
    -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
  • Ambient temperature (storage/transport)
    -40 °C ... 85 °C
  • Max. permissible relative humidity (operation)
    95 % (at 25 °C, non-condensing)
  • Ambient temperature (start-up type tested)
    -40 °C
  • Degree of pollution
    2
  • Climatic class
    3K3 (in acc. with EN 60721)
  • Installation height
    6000 m
  • Input voltage range
    85 V AC ... 264 V AC
  • Nominal input voltage range
    100 V AC ... 240 V AC
  • Dielectric strength maximum
    300 V AC
  • Frequency range DC
    0 Hz
  • AC frequency range
    45 Hz ... 65 Hz
  • Discharge current to PE
    < 3.5 mA
  • Nominal power consumption
    311 VA
  • Current consumption
    2.4 A (120 V AC)
  • Inrush current
    < 20 A (typical)
  • Input fuse
    12 A (slow-blow, internal)
  • Recommended breaker for input protection
    10 A ... 16 A (AC: Characteristics B, C, D, K)
  • Mains buffering time
    typ. 40 ms (120 V AC)
  • Type of protection
    Transient surge protection
  • Protective circuit/component
    Varistor
  • Nominal output voltage
    12 V DC ±1 %
  • Setting range of the output voltage (USet)
    5 V DC ... 18 V DC (> 12 V DC, constant capacity restricted)
  • Nominal output current (IN)
    20 A (-25 °C ... 60 °C)
  • POWER BOOST (IBoost)
    26 A (-25°C ... 40°C permanent )
  • Selective Fuse Breaking (ISFB)
    120 A (12 ms)
  • Connection in parallel
    Yes, for redundancy and increased capacity
  • Derating
    60 °C ... 70 °C (2.5%/K)
  • Protection against overvoltage at the output (OVP)
    < 25 V DC
  • Control deviation
    < 1 % (change in load, static 10 % ... 90 %)
  • Residual ripple
    < 50 mVPP (with nominal values)
  • Power loss nominal load max.
    29 W
  • Net weight
    1.5 kg
  • Efficiency
    > 90 % (for 230 V AC and nominal values)
  • Insulation voltage output / PE
    500 V DC (routine test)
  • Protection class
    I
  • Mounting position
    horizontal DIN rail NS 35, EN 60715
  • Conductor cross section solid min.
    0.2 mm²
  • Conductor cross section flexible min.
    0.2 mm²
  • Conductor cross section AWG max.
    10
  • Stripping length
    7 mm
  • Screw thread
    M3
  • Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
  • Standard – Safety extra-low voltage
    IEC 60950-1 (SELV) and EN 60204-1 (PELV)
  • Standard - Safe isolation
    DIN VDE 0100-410
  • Standard - Equipment safety
    GS (tested safety)
  • Rail applications
    EN 50121-4
  • Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
  • Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
  • Contact discharge
    8 kV (Test Level 4)
  • Discharge in air
    15 kV (Test Level 4)
  • Comments
    Criterion A
  • Fast transients (burst)
    EN 61000-4-4
  • Input
    2 kV (Test Level 3 - symmetrical)
  • Conducted interference
    EN 61000-4-6
  • Voltage
    10 V (Test Level 3)
  • Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
  • REACh SVHC
    Lead 7439-92-1
  • ECLASS 10.0.1
    27040701
  • ECLASS 4.0
    27040700
  • ECLASS 4.1
    27040700
  • ECLASS 6.0
    27049000
  • ETIM 2.0
    EC001039
  • ECLASS 9.0
    27040701
  • ETIM 4.0
    EC002540
  • UNSPSC 7.0901
    39121004
  • UNSPSC 11
    39121004
  • UNSPSC 12.01
    39121004
  • UNSPSC 20.0
    39121004
  • UNSPSC 21.0
    39121004
  • UNSPSC 18.0
    39121004
  • UNSPSC 19.0
    39121004

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price within minutes.

Stock:

7

Select Qty:

Average response time: 11 minutes

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

What can I help you find today?

Recommended parts

UBC10.241

UBC10.241

PULS UBC10.241 is an Uninterruptible Power Supply (UPS) control module within the U-series, featuring a built-in battery with a 50% power reserve and a green status LED. This module is housed in aluminium and utilizes spring-clamp connections for installation. It measures W123mm x H124mm x D119mm and operates on a supply voltage range of 22.5Vdc to 30Vdc, with a nominal 24Vdc. The rated current is 10A at 22.5Vdc and can reach up to 15A in buffer mode for less than 5 seconds at full output voltage. It supports DIN rail mounting and can operate in ambient air temperatures ranging from 0 to +40°C. The current consumption is 1.1A at a 24Vdc input, and it is designed for DC networks. Visual position indicators include Ready, Buffering, Inhibit, and Replace Battery. Protection functions include output overvoltage protection with a typical 32Vdc and a maximum of 35Vdc, and overload/short-circuit protection with a minimum of 17.9A and a maximum of 21A at load impedance. It is advised not to use the DC-UPS in parallel to increase output power, but paralleling two units for 1+1 redundancy is possible for higher system reliability. The output voltage is regulated at 22.5Vdc in buffer mode with a 23Vdc turn-ON. The efficiency is rated at 0.978 with a 24Vdc input, and the rated power is 360W at 24Vdc and 240W/360W in buffer mode. Power dissipation/losses are 2.9W with a 24Vdc input at 0A output current and 5.5W at 10A output current. Ripple is maintained at 20mVpp across a frequency range of 20Hz to 20MHz at 50Ω. The electrical durability is rated at 137400 hours at 40°C with a 10A output and 24Vdc input, equivalent to 15 years or 131400 hours at both 40°C with a 5A output and 25°C with a 10A output.

Puls

1