FCS-G1/2A4P-VRX/24VDC Turck Flow Sensors

Turck FCS-G1/2A4P-VRX/24VDC FCS-G1/2A4P-VRX/24VDC Flow Monitoring, Immersion Sensor with Integrated Processor
Turck

Part#:FCS-G1/2A4P-VRX/24VDC

Manufacturer:Turck

Alt. Part#:6870096

Product Lifecycle:Active

Get a quick Quote!

FCS-G1/2A4P-VRX/24VDC Flow Monitoring, Immersion Sensor with Integrated Processor

About the manufacturer: Turck is one of the manufacturers that offers Flow Sensors that you can order at Powermatic Associates site. Turck is a leading provider of sensor, fieldbus, and connectivity technologies, along with interface technology, human-machine interfaces (HMI), and RFID systems. We offer innovative solutions for factory and process automation requirements, guaranteeing top-notch performance.

Check out the FCS-G1/2A4P-VRX/24VDC Turck price in the box on the right side or send a quick quote.

Product Details

  • Weight
    528 g
  • RoHS
    Yes
  • Country Of Origin
    DEU
  • HTS Code
    9026102040
  • Housing material
    Plastic, PBT
  • Sensor material
    Stainless steel
  • Protection class
    IP68
  • Medium temperature
    -20…+80 °C
  • Electrical connection
    Cable
  • Output function
    Complementary contact, Relay output
  • Cable length (L)
    2.0  m
  • Operating voltage
    19.2…28.8 VDC
  • Operating principle
    Calorimetric
  • Function
    Flow monitoring
  • Process connection
    G 1/2”
  • Design
    Immersion
  • Medium
    liquids

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.


FCS-G1/2A4P-VRX/24VDC Description

Turck FCS-G1/2A4P-VRX/24VDC is a sensor designed for flow monitoring, featuring a PBT (Polybutylene Terephthalate) housing, stainless steel 316Ti wetted parts, and a stainless steel 303 connector. It operates within an ambient air temperature range of -20°C to +80°C and offers a degree of protection rated at IP68. This sensor includes 1 x digital output (SPDT / NO/NC / 1C/O rly. dry contact) and has a rectangular body shape. It is capable of detecting flow rates from 1cm/s to 1.5m/s in water and 3cm/s to 3m/s in oil. As part of the FCS series, it functions as an instrumentation insertion probe flow monitor sensor/switch. The connection is facilitated by a pre-wired 2m / 6.5ft cable with bare end flying leads and a G1/2" (1/2" BSPP) threaded male process port. It can withstand pressure up to 100bar (1450psi) and is designed for a supply voltage range of 19.2-28.8Vdc (24Vdc nom.). The medium temperature range for operation is also -20°C to +80°C.



Related documents FCS-G1/2A4P-VRX/24VDC Specs

Manufacturer warranty

Get a quick Quote!

Request a quote, and we will send you price and availability within minutes.

Select Qty:

Average response time: 11 minutes

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

Relevant products

What can I help you find today?

Recommended parts

UBC10.241

UBC10.241

PULS UBC10.241 is an Uninterruptible Power Supply (UPS) control module within the U-series, featuring a built-in battery with a 50% power reserve and a green status LED. This module is housed in aluminium and utilizes spring-clamp connections for installation. It measures W123mm x H124mm x D119mm and operates on a supply voltage range of 22.5Vdc to 30Vdc, with a nominal 24Vdc. The rated current is 10A at 22.5Vdc and can reach up to 15A in buffer mode for less than 5 seconds at full output voltage. It supports DIN rail mounting and can operate in ambient air temperatures ranging from 0 to +40°C. The current consumption is 1.1A at a 24Vdc input, and it is designed for DC networks. Visual position indicators include Ready, Buffering, Inhibit, and Replace Battery. Protection functions include output overvoltage protection with a typical 32Vdc and a maximum of 35Vdc, and overload/short-circuit protection with a minimum of 17.9A and a maximum of 21A at load impedance. It is advised not to use the DC-UPS in parallel to increase output power, but paralleling two units for 1+1 redundancy is possible for higher system reliability. The output voltage is regulated at 22.5Vdc in buffer mode with a 23Vdc turn-ON. The efficiency is rated at 0.978 with a 24Vdc input, and the rated power is 360W at 24Vdc and 240W/360W in buffer mode. Power dissipation/losses are 2.9W with a 24Vdc input at 0A output current and 5.5W at 10A output current. Ripple is maintained at 20mVpp across a frequency range of 20Hz to 20MHz at 50Ω. The electrical durability is rated at 137400 hours at 40°C with a 10A output and 24Vdc input, equivalent to 15 years or 131400 hours at both 40°C with a 5A output and 25°C with a 10A output.

Puls