LC1DT406BD Schneider Electric Industrial Automation Components

LC1DT406BD on Powermatic Associates
Schneider Electric

Part#:LC1DT406BD

Manufacturer:Schneider Electric

Category:Industrial Automation Components

Product Lifecycle:Active

In-stock parts: 6

Dec 21, 2024

Schneider Electric LC1DT406BD is a magnetic contactor from the Deca sub-range, designed with ring-lugs connections and equipped with 4 poles (4NO). It has a rated current of 40A (AC-1) and is suitable for DIN rail mounting. The dimensions include a net width of 45 mm and it offers a degree of protection rated at IP20. This contactor operates with a control voltage (DC) range of 18-30Vdc, nominally at 24Vdc, and includes 1 normally open (NO) and 1 normally closed (NC) auxiliary contacts, both of the instantaneous type. It is designed to withstand a rated impulse voltage (Uimp) of 6 kV and has a mechanical durability of 15,000,000 operations at no load. The rated voltage (AC) for phase-to-phase connections is up to 690 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1DT406BD Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    UL LROS (Lloyds register of shipping) BV CSA GL RINA CCC GOST DNV
  • Standards
    CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • [Ui] Rated Insulation Voltage
    Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1
  • [Icw] Rated Short-Time Withstand Current
    50 A 104 °F (40 °C) - 10 min power circuit 120 A 104 °F (40 °C) - 1 min power circuit 240 A 104 °F (40 °C) - 10 s power circuit 380 A 104 °F (40 °C) - 1 s power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circ
  • Tightening Torque
    Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 15.93 lbf.in (1.8 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Power circuit
  • Irms Rated Making Capacity
    140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 450 A 440 V power circuit IEC 60947
  • Control Circuit Voltage Limits
    0.1...0.25 Uc -40…158 °F (-40…70 °C) drop-out DC 0.7...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
  • Associated Fuse Rating
    10 A gG signalling circuit IEC 60947-5-1 63 A gG <= 690 V type 1 power circuit 40 A gG <= 690 V type 2 power circuit
  • Mounting Support
    Rail Plate
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Auxiliary Contacts Type
    Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • Connections - Terminals
    Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.31 in (8 mm))
  • Operating Time
    16...24 ms opening 53.55...72.45 ms closing
  • [Ue] Rated Operational Voltage
    Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current
    10 A 140 °F (60 °C) signalling circuit 40 A 140 °F (60 °C) power circuit
  • Non-Overlap Time
    1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • Insulation Resistance
    > 10 MOhm for signalling circuit
  • Signalling Circuit Frequency
    25...400 Hz
  • Minimum Switching Current
    5 mA signalling circuit
  • Minimum Switching Voltage
    17 V signalling circuit
  • Maximum Operating Rate
    3600 cyc/h 140 °F (60 °C)
  • Time Constant
    28 ms
  • Coil Technology
    Built-in bidirectional peak limiting diode suppressor
  • Inrush Power In W
    5.4 W 68 °F (20 °C))
  • Hold-In Power Consumption In W
    5.4 W 68 °F (20 °C)
  • Mechanical Durability
    30 Mcycles
  • Front Cover
    With
  • Power Dissipation Per Pole
    3.2 W AC-1
  • Average Impedance
    2 mOhm - Ith 40 A 50 Hz power circuit
  • Electrical Durability
    1.4 Mcycles 40 A AC-1 <= 440 V
  • Rated Breaking Capacity
    450 A 440 V power circuit IEC 60947
  • [Uimp] Rated Impulse Withstand Voltage
    6 kV IEC 60947
  • Control Circuit Type
    DC standard
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • [Ie] Rated Operational Current
    40 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
  • [Uc] Control Circuit Voltage
    24 V DC
  • Overvoltage Category
    III
  • Poles Description
    4P
  • Utilisation Category
    AC-1
  • Power Pole Contact Composition
    4 NO
  • Device Short Name
    LC1D
  • Contactor Application
    Resistive load
  • Range
    TeSys
  • Product Or Component Type
    Contactor
  • Product Name
    TeSys D

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



This item can ship within 24h!

Manufacturer warranty

$245.70

Stock:

6

Select Qty:

$245.70

$245.70 each

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?