LC1D096BL Schneider Electric Industrial Automation Components
Part#:LC1D096BL
Manufacturer:Schneider Electric
Product Lifecycle:Active
In-stock parts: 14
Nov 20, 2024
IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, 3 phase, 3 pole, 3 NO, low consumption 24VDC coil, open style
About the manufacturer: Schneider Electric is one of the manufacturers that offers Industrial Automation Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.
Check out the LC1D096BL Schneider Electric price in the box on the right side or send a quick quote.
Product Details
- Product Certifications BV GL UL GOST RINA CCC CSA DNV LROS (Lloyds register of shipping)
- [Ui] Rated Insulation Voltage Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current 105 A 104 °F (40 °C) - 10 s power circuit 210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circu
- Motor Power HP (UL / CSA) 1 hp 230/240 V at AC 50/60 Hz for 1 phase 2 hp 200/208 V at AC 50/60 Hz for 3 phase 2 hp 230/240 V at AC 50/60 Hz for 3 phase 5 hp 460/480 V at AC 50/60 Hz for 3 phase 7.5 hp 575/600 V at AC 50/60 Hz for 3 phase 0.33 hp 115 V at A
- Motor Power Kw 2.2 kW 220...230 V AC 50/60 Hz AC-3) 4 kW 380...400 V AC 50/60 Hz AC-3) 4 kW 415...440 V AC 50/60 Hz AC-3) 5.5 kW 500 V AC 50/60 Hz AC-3) 5.5 kW 660...690 V AC 50/60 Hz AC-3) 2.2 kW 400 V AC 50/60 Hz AC-4)
- Standards CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
- Tightening Torque Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 6 mm M3.5 Control circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals Philips No 2 M3.5 Power circuit 15.05 lbf.in (1.7 N.m) lugs-ring terminals flat Ø 8 mm M3.5 Power circuit
- Control Circuit Voltage Limits 0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.8...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
- Irms Rated Making Capacity 250 A 440 V power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
- Utilisation Category AC-1 AC-3 AC-4
- Associated Fuse Rating 10 A gG signalling circuit IEC 60947-5-1 25 A gG <= 690 V type 1 power circuit 20 A gG <= 690 V type 2 power circuit
- Connections - Terminals Control circuit lugs-ring terminals 0.31 in (8 mm)) Power circuit lugs-ring terminals 0.31 in (8 mm))
- Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
- Auxiliary Contacts Type Mechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
- [Ie] Rated Operational Current 9 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
- Contactor Application Resistive load Motor control
- Safety Reliability Level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Ith] Conventional Free Air Thermal Current 25 A 140 °F (60 °C) power circuit 10 A 140 °F (60 °C) signalling circuit
- Power Dissipation Per Pole 1.56 W AC-1 0.2 W AC-3
- Electrical Durability 0.6 Mcycles 25 A AC-1 <= 440 V 2 Mcycles 9 A AC-3 <= 440 V
- Mounting Support Rail Plate
- Operating Time 65.45...88.55 ms closing 20...30 ms opening
- [Ue] Rated Operational Voltage Power circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
- Minimum Switching Current 5 mA signalling circuit
- Maximum Operating Rate 3600 cyc/h 140 °F (60 °C)
- Insulation Resistance > 10 MOhm signalling circuit
- Minimum Switching Voltage 17 V signalling circuit
- Signalling Circuit Frequency 25...400 Hz
- Inrush Power In W 2.4 W 68 °F (20 °C))
- Hold-In Power Consumption In W 2.4 W 68 °F (20 °C)
- Time Constant 40 ms
- Mechanical Durability 30 Mcycles
- Coil Technology Built-in bidirectional peak limiting diode suppressor
- Front Cover With
- Rated Breaking Capacity 250 A 440 V power circuit IEC 60947
- Average Impedance 2.5 mOhm - Ith 25 A 50 Hz power circuit
- Overvoltage Category III
- Auxiliary Contact Composition 1 NO + 1 NC
- [Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
- Control Circuit Type DC low consumption
- [Uc] Control Circuit Voltage 24 V DC
- Device Short Name LC1D
- Product Or Component Type Contactor
- Power Pole Contact Composition 3 NO
- Poles Description 3P
- Range TeSys
- Product Name TeSys D
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Related documents LC1D096BL Specs
This item can ship within 24h!
Manufacturer warranty
$136.47
Stock:
14
Select Qty:
$136.47
$136.47 each
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
Relevant products
What can I help you find today?