Square D by Schneider Electric HDF36035 is a Moulded Case Circuit Breaker (MCCB) within the PowerPacT HDF sub-range, featuring a PowerPact H-Frame 150 TMD design. It is a 3-pole (3P) device with a rated current of 35A and offers thermal protection for overload and magnetic protection for short-circuit scenarios. This MCCB has a rated insulation voltage (Ui) of 750 V, with AC rated voltages of 600Vac and 600Y/347Vac, and a DC rated voltage of 250Vdc. It is designed for individual unit mount on plate with a Term. nut kit for fixed busbar connection on both line and load sides. The HDF36035 has a net height of 163 mm, a net width of 104 mm, and a net depth of 86 mm, featuring an IP40 degree of protection. Its operating mode is manual toggle, with over-current protection settings fixed at 35A, short-circuit hold current fixed at 400A, and short-circuit trip current fixed at 850A. The rated operating voltage (Ue) is 690 V, with a rated impulse voltage (Uimp) of 8 kV. The trip current rating is 35 AT, with a frame current rating of 150 AF. Its short circuit breaking rating varies with voltage, including 25kA at 240Vac, 18kA at 480Vac and 480Y/277Vac, 14kA at 600Vac and 600Y/347Vac, and 20kA at 250Vdc, all according to UL489 standards. The trip unit type is thermal-magnetic (fixed) with no display, and it falls under utilisation category A.
Product Details
- Electrical Connection Busbar connection line Busbar connection load
- Continuous Current Rating 80 %
- Width 4.12 in (104.65 mm)
- Depth 4.36 in (110.74 mm)
- Tightening Torque 44.25 lbf.in (5 N.m) 0.00…0.15 in² (2.5…95 mm²) (AWG 14...AWG 3/0)
- Breaking Capacity Code D
- Height 6.4 in (162.56 mm)
- Magnetic Tripping Current 850 A
- Magnetic Hold Current 400 A
- Mounting Mode Unit mount
- Number Of Poles 3P
- Line Rated Current 35 A
- Product Or Component Type Circuit breaker
- Range Of Product PowerPact H
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
HDF36035 Related Documents
Similar products from: Schneider Electric Electronic Components
Manufacturer warranty
HDF36035 Schneider Electric
Get a quick Quote!
Request a quote, and we will send you price within minutes.
Stock:
Select Qty:
Average response time: 11 minutes
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
Compare HDF36035 with other Electronic Components products
Electrical Connection
Continuous Current Rating
Width
Depth
Tightening Torque
Breaking Capacity Code
Height
Magnetic Tripping Current
Magnetic Hold Current
Mounting Mode
Selected product

HDF36035
Schneider Electric
Square D by Schneider Electric HDF36035 is a Moulded Case Circuit Breaker (MCCB) within the PowerPac...
Electrical ConnectionBusbar connection line Busba...
Continuous Current Rating80 %
Width4.12 in (104.65 mm)
Depth4.36 in (110.74 mm)
Tightening Torque44.25 lbf.in (5 N.m) 0.00…0....
Breaking Capacity CodeD
Height6.4 in (162.56 mm)
Magnetic Tripping Current850 A
Magnetic Hold Current400 A
Mounting ModeUnit mount
About the manufacturer
Powermatic Associates is an authorized Schneider Electric distributor, proudly offering a diverse portfolio of innovative solutions tailored to meet the dynamic needs of today's industrial landscape. Schneider Electric stands as a global leader in energy management and automation, providing cutting-edge products and services that drive efficiency and sustainability across a variety of sectors. The...
Recently viewed products
Relevant products
FAQ
1 in stock
Square D by Schneider Electric HDF36035 is a Moulded Case Circuit Breaker (MCCB) within the PowerPacT HDF sub-range, featuring a PowerPact H-Frame 150 TMD design. It is a 3-pole (3P) device with a rated current of 35A and offers thermal protection for overload and magnetic protection for short-circuit scenarios. This MCCB has a rated insulation voltage (Ui) of 750 V, with AC rated voltages of 600Vac and 600Y/347Vac, and a DC rated voltage of 250Vdc. It is designed for individual unit mount on plate with a Term. nut kit for fixed busbar connection on both line and load sides. The HDF36035 has a net height of 163 mm, a net width of 104 mm, and a net depth of 86 mm, featuring an IP40 degree of protection. Its operating mode is manual toggle, with over-current protection settings fixed at 35A, short-circuit hold current fixed at 400A, and short-circuit trip current fixed at 850A. The rated operating voltage (Ue) is 690 V, with a rated impulse voltage (Uimp) of 8 kV. The trip current rating is 35 AT, with a frame current rating of 150 AF. Its short circuit breaking rating varies with voltage, including 25kA at 240Vac, 18kA at 480Vac and 480Y/277Vac, 14kA at 600Vac and 600Y/347Vac, and 20kA at 250Vdc, all according to UL489 standards. The trip unit type is thermal-magnetic (fixed) with no display, and it falls under utilisation category A.
Similar products from: Electronic Components
What can I help you find today?