LC1F500M7 Schneider Electric Electronic Components

Schneider Electric LC1F500M7 Schneider Electric LC1F500M7 is a high-power magnetic contactor within the F sub-range, designed for surface mounting. It features a 3-pole (3P; 3NO) configuration and supports ring-lugs/bar connections. This contactor is rated for currents up to 700A in AC-1 applications and 500A in AC-3 applications at 440Vac. The control voltage (AC) ranges from 187-242Vac (220Vac nominal; 40-400Hz; 0.85...1.1 x Uc), with a rated operating voltage (Ue) of 1000 V. It has no Normally Open (NO) or Normally Closed (NC) auxiliary contacts. The rated impulse voltage (Uimp) is 8 kV. The rated active power (kW) varies from 147kW at 220-230Vac to 335kW at 1000Vac in AC-3 applications. Its mechanical durability is rated at 10 million operations at no load, and the rated voltage (AC) phase-to-phase is 1000 V.
Schneider Electric

Part#:LC1F500M7

Manufacturer:Schneider Electric

Product Lifecycle:Active

Get a quick Quote!

Schneider Electric LC1F500M7 is a high-power magnetic contactor within the F sub-range, designed for surface mounting. It features a 3-pole (3P; 3NO) configuration and supports ring-lugs/bar connections. This contactor is rated for currents up to 700A in AC-1 applications and 500A in AC-3 applications at 440Vac. The control voltage (AC) ranges from 187-242Vac (220Vac nominal; 40-400Hz; 0.85...1.1 x Uc), with a rated operating voltage (Ue) of 1000 V. It has no Normally Open (NO) or Normally Closed (NC) auxiliary contacts. The rated impulse voltage (Uimp) is 8 kV. The rated active power (kW) varies from 147kW at 220-230Vac to 335kW at 1000Vac in AC-3 applications. Its mechanical durability is rated at 10 million operations at no load, and the rated voltage (AC) phase-to-phase is 1000 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Electronic Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1F500M7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Motor Power Kw
    250 kW 380...400 V AC 50/60 Hz AC-3) 280 kW 415 V AC 50/60 Hz AC-3) 295 kW 440 V AC 50/60 Hz AC-3) 355 kW 500 V AC 50/60 Hz AC-3) 335 kW 660...690 V AC 50/60 Hz AC-3) 335 kW 1000 V AC 50/60 Hz AC-3) 147 kW 220...230 V AC 50/6
  • Product Certifications
    CSA CB RMRoS ABS LROS (Lloyds register of shipping) UL RINA BV DNV UKCA
  • [Icw] Rated Short-Time Withstand Current
    4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min
  • Standards
    EN 60947-4-1 IEC 60947-1 EN 60947-1 JIS C8201-4-1 IEC 60947-4-1
  • Motor Power Range
    250…500 kW 380…440 V 3 phase 110…220 kW 380…440 V 3 phase 110…220 kW 200…240 V 3 phase 250…500 kW 480…500 V 3 phase
  • Connections - Terminals
    Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
  • Utilisation Category
    AC-1 AC-4 AC-3
  • Tightening Torque
    Control circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
  • Operating Time
    40...65 ms closing 100...170 ms opening
  • [Ie] Rated Operational Current
    700 A 104 °F (40 °C)) <= 440 V AC AC-1 500 A 131 °F (55 °C)) <= 440 V AC AC-3
  • Contactor Application
    Motor control Resistive load
  • Power Dissipation Per Pole
    88 W AC-1 45 W AC-3
  • [Ui] Rated Insulation Voltage
    1000 V IEC 60947-4-1 1500 V VDE 0110 group C
  • [Ue] Rated Operational Voltage
    <= 1000 V AC 50/60 Hz <= 460 V DC
  • Control Circuit Voltage Limits
    Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
  • Associated Fuse Rating
    500 A aM <= 440 V 800 A gG <= 440 V
  • Contactor Coil Voltage
    220 V AC standard
  • Motor Starter Type
    Direct on-line contactor
  • Heat Dissipation
    18 W
  • Compatibility Code
    LC1F
  • Maximum Operating Rate
    2400 cyc/h 131 °F (55 °C)
  • Mechanical Durability
    10 Mcycles
  • Hold-In Power Consumption In VA
    18 VA 40...400 Hz 0.9 68 °F (20 °C))
  • Inrush Power In VA
    1100 VA 40...400 Hz 0.9 68 °F (20 °C))
  • Mounting Support
    Plate
  • Rated Breaking Capacity
    4000 A IEC 60947-4-1
  • [Ith] Conventional Free Air Thermal Current
    700 A 104 °F (40 °C)
  • Overvoltage Category
    III
  • [Uimp] Rated Impulse Withstand Voltage
    8 kV
  • [Uc] Control Circuit Voltage
    220 V AC 40...400 Hz
  • Average Impedance
    0.18 mOhm - Ith 700 A 50 Hz
  • Poles Description
    3P
  • Power Pole Contact Composition
    3 NO
  • Device Short Name
    LC1F
  • Product Name
    TeSys F
  • Product Or Component Type
    Contactor
  • Range
    TeSys

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



Manufacturer warranty

$4,970.00

Request a quote, and we will send availability within minutes.

Select Qty:

$4,970.00

$4,970.00 each

Average response time: 11 minutes

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

Relevant products

What can I help you find today?

Recommended parts

UBC10.241

UBC10.241

PULS UBC10.241 is an Uninterruptible Power Supply (UPS) control module within the U-series, featuring a built-in battery with a 50% power reserve and a green status LED. This module is housed in aluminium and utilizes spring-clamp connections for installation. It measures W123mm x H124mm x D119mm and operates on a supply voltage range of 22.5Vdc to 30Vdc, with a nominal 24Vdc. The rated current is 10A at 22.5Vdc and can reach up to 15A in buffer mode for less than 5 seconds at full output voltage. It supports DIN rail mounting and can operate in ambient air temperatures ranging from 0 to +40°C. The current consumption is 1.1A at a 24Vdc input, and it is designed for DC networks. Visual position indicators include Ready, Buffering, Inhibit, and Replace Battery. Protection functions include output overvoltage protection with a typical 32Vdc and a maximum of 35Vdc, and overload/short-circuit protection with a minimum of 17.9A and a maximum of 21A at load impedance. It is advised not to use the DC-UPS in parallel to increase output power, but paralleling two units for 1+1 redundancy is possible for higher system reliability. The output voltage is regulated at 22.5Vdc in buffer mode with a 23Vdc turn-ON. The efficiency is rated at 0.978 with a 24Vdc input, and the rated power is 360W at 24Vdc and 240W/360W in buffer mode. Power dissipation/losses are 2.9W with a 24Vdc input at 0A output current and 5.5W at 10A output current. Ripple is maintained at 20mVpp across a frequency range of 20Hz to 20MHz at 50Ω. The electrical durability is rated at 137400 hours at 40°C with a 10A output and 24Vdc input, equivalent to 15 years or 131400 hours at both 40°C with a 5A output and 25°C with a 10A output.

Puls