LC1F225G7 Schneider Electric Electronic Components

Schneider Electric LC1F225G7 Schneider Electric LC1F225G7 is a high-power magnetic contactor within the F sub-range, designed for surface mounting. It features a 3-pole (3P; 3NO) configuration and supports ring-lugs/bar connections. The contactor is rated for currents of 315A under AC-1 conditions and 225A at 440Vac under AC-3 conditions. It operates with a control voltage (AC) range of 102-132Vac (120Vac nominal; 40-400Hz; 0.85...1.1 x Uc) and has a rated operating voltage (Ue) of up to 1000 V. This model comes without normally open (NO) or normally closed (NC) auxiliary contacts. It is capable of handling rated impulse voltage (Uimp) of 8 kV and supports rated active power (kW) of 63kW at 220-230Vac, 110kW at 380-400Vac, 415Vac, and 440Vac, 129kW at 500Vac, and 660-690Vac, and 100kW at 1000Vac, all under AC-3 conditions. The mechanical durability of the LC1F225G7, at no load, is rated at 10,000,000 operations, and it can handle a phase-to-phase rated voltage (AC) of 1000 V.
Schneider Electric

Part#:LC1F225G7

Manufacturer:Schneider Electric

Product Lifecycle:Active

Get a quick Quote!

Schneider Electric LC1F225G7 is a high-power magnetic contactor within the F sub-range, designed for surface mounting. It features a 3-pole (3P; 3NO) configuration and supports ring-lugs/bar connections. The contactor is rated for currents of 315A under AC-1 conditions and 225A at 440Vac under AC-3 conditions. It operates with a control voltage (AC) range of 102-132Vac (120Vac nominal; 40-400Hz; 0.85...1.1 x Uc) and has a rated operating voltage (Ue) of up to 1000 V. This model comes without normally open (NO) or normally closed (NC) auxiliary contacts. It is capable of handling rated impulse voltage (Uimp) of 8 kV and supports rated active power (kW) of 63kW at 220-230Vac, 110kW at 380-400Vac, 415Vac, and 440Vac, 129kW at 500Vac, and 660-690Vac, and 100kW at 1000Vac, all under AC-3 conditions. The mechanical durability of the LC1F225G7, at no load, is rated at 10,000,000 operations, and it can handle a phase-to-phase rated voltage (AC) of 1000 V.

About the manufacturer: Schneider Electric is one of the manufacturers that offers Electronic Components that you can order at Powermatic Associates site. We provide digital solutions for energy and automation that improve efficiency and support sustainability. Our comprehensive solutions include cutting-edge energy technologies, real-time automation, software, and services for residential, commercial, and industrial settings.

Check out the LC1F225G7 Schneider Electric price in the box on the right side or send a quick quote.

Product Details

  • Product Certifications
    CB LROS (Lloyds register of shipping) CSA RINA BV DNV RMRoS ABS UL UKCA
  • Motor Power Kw
    110 kW 380...400 V AC 50/60 Hz AC-3) 110 kW 415 V AC 50/60 Hz AC-3) 110 kW 440 V AC 50/60 Hz AC-3) 129 kW 500 V AC 50/60 Hz AC-3) 129 kW 660...690 V AC 50/60 Hz AC-3) 63 kW 220...230 V AC 50/60 Hz AC-3) 40 kW 400 V AC 50/60 H
  • [Icw] Rated Short-Time Withstand Current
    1800 A 104 °F (40 °C) - 10 s 1000 A 104 °F (40 °C) - 30 s 850 A 104 °F (40 °C) - 1 min 560 A 104 °F (40 °C) - 3 min 440 A 104 °F (40 °C) - 10 min
  • Standards
    IEC 60947-4-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1
  • Motor Power Range
    55…100 kW 200…240 V 3 phase 110…220 kW 480…500 V 3 phase 110…220 kW 380…440 V 3 phase
  • Connections - Terminals
    Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
  • Utilisation Category
    AC-1 AC-4 AC-3
  • Operating Time
    35 ms closing at Uc) 130 ms opening at Uc)
  • Contactor Application
    Motor control Resistive load
  • [Ui] Rated Insulation Voltage
    1000 V IEC 60947-4-1 1500 V VDE 0110 group C
  • [Ue] Rated Operational Voltage
    <= 460 V DC <= 690 V AC 50/60 Hz
  • Associated Fuse Rating
    315 A gG <= 440 V 250 A aM <= 440 V
  • [Ie] Rated Operational Current
    315 A 104 °F (40 °C)) <= 440 V AC-1 225 A 131 °F (55 °C)) <= 440 V AC-3
  • Control Circuit Voltage Limits
    Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 40...400 Hz 131 °F (55 °C))
  • Power Dissipation Per Pole
    32 W AC-1 16 W AC-3
  • Tightening Torque
    Control circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
  • Maximum Operating Rate
    2400 cyc/h 131 °F (55 °C)
  • Heat Dissipation
    8…9.8 W
  • Average Impedance
    0.32 mOhm - Ith 315 A 50 Hz
  • Contactor Coil Voltage
    120 V AC standard
  • Motor Starter Type
    Direct on-line contactor
  • Mechanical Durability
    10 Mcycles
  • Compatibility Code
    LC1F
  • Hold-In Power Consumption In VA
    9.9 VA 40...400 Hz 0.9 68 °F (20 °C))
  • Inrush Power In VA
    1070 VA 40...400 Hz 0.9 68 °F (20 °C))
  • Mounting Support
    Plate
  • Rated Breaking Capacity
    1800 A IEC 60947-4-1
  • [Ith] Conventional Free Air Thermal Current
    315 A 104 °F (40 °C)
  • [Uimp] Rated Impulse Withstand Voltage
    8 kV
  • Overvoltage Category
    III
  • [Uc] Control Circuit Voltage
    120 V AC 40...400 Hz
  • Power Pole Contact Composition
    3 NO
  • Poles Description
    3P
  • Product Or Component Type
    Contactor
  • Device Short Name
    LC1F
  • Product Name
    TeSys F
  • Range
    TeSys

Product condition

New Factory Sealed

New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.



Manufacturer warranty

$1,059.00

Request a quote, and we will send availability within minutes.

Select Qty:

$1,059.00

$1,059.00 each

Average response time: 11 minutes

Worldwide Shipping and Delivery


Secure Payment Processing


Warranty


Responsive Customer Support

Got Questions? We've Got Answers!


Need more details?

Feel free to chat with us

Relevant products

What can I help you find today?

Recommended parts

UBC10.241

UBC10.241

PULS UBC10.241 is an Uninterruptible Power Supply (UPS) control module within the U-series, featuring a built-in battery with a 50% power reserve and a green status LED. This module is housed in aluminium and utilizes spring-clamp connections for installation. It measures W123mm x H124mm x D119mm and operates on a supply voltage range of 22.5Vdc to 30Vdc, with a nominal 24Vdc. The rated current is 10A at 22.5Vdc and can reach up to 15A in buffer mode for less than 5 seconds at full output voltage. It supports DIN rail mounting and can operate in ambient air temperatures ranging from 0 to +40°C. The current consumption is 1.1A at a 24Vdc input, and it is designed for DC networks. Visual position indicators include Ready, Buffering, Inhibit, and Replace Battery. Protection functions include output overvoltage protection with a typical 32Vdc and a maximum of 35Vdc, and overload/short-circuit protection with a minimum of 17.9A and a maximum of 21A at load impedance. It is advised not to use the DC-UPS in parallel to increase output power, but paralleling two units for 1+1 redundancy is possible for higher system reliability. The output voltage is regulated at 22.5Vdc in buffer mode with a 23Vdc turn-ON. The efficiency is rated at 0.978 with a 24Vdc input, and the rated power is 360W at 24Vdc and 240W/360W in buffer mode. Power dissipation/losses are 2.9W with a 24Vdc input at 0A output current and 5.5W at 10A output current. Ripple is maintained at 20mVpp across a frequency range of 20Hz to 20MHz at 50Ω. The electrical durability is rated at 137400 hours at 40°C with a 10A output and 24Vdc input, equivalent to 15 years or 131400 hours at both 40°C with a 5A output and 25°C with a 10A output.

Puls