8059847 Festo Electrical Peripheral Devices
Part#:8059847
Manufacturer:Festo
Alt. Part#:CPX-4AE-4AA-H
Product Lifecycle:Active
Get a quick Quote!
input module CPX-4AE-4AA-H HART-capable, configurable as input or output. Dimensions W x L x H: (* (incl. interlinking block and connection technology), * 50 mm x 107 mm x 70 mm), Grid dimension: 50 mm, Number of selectable analogue inputs/outputs: 4, Dia
About the manufacturer: Festo is one of the manufacturers that offers Electrical Peripheral Devices that you can order at Powermatic Associates site. Festo Corp. has been a top supplier of automation and intelligent automation solutions for more than four decades in the United States and eight decades globally. The company is committed to transforming the manufacturing sector and enhancing business efficiency.
Check out the 8059847 Festo price in the box on the right side or send a quick quote.
Product Details
- Min. available sensor voltage 20.7 V at 20 mA
- Diagnostics Wire break per channel Overflow/underflow
- Repetition accuracy 0.05 % at 25 °C
- Corrosion resistance class (CRC) 1 - Low corrosion stress (when installed)
- Data format 15 bit + sign Scalable to 15 bits
- Housing material PA-reinforced PC
- Dimensions W x L x H (incl. interlinking block and connection system) 50 mm x 107 mm x 70 mm
- Signal range 0 - 20 mA 4–20 mA with HART
- Max. short circuit current 22 mA
- Reverse polarity protection for all electrical connections
- Fuse protection (short circuit) Internal electronic fuse per channel
- Basic error limit at 25°C ±0.1 %
- Electrical isolation between channels no
- Product weight 77.4 g
- Type of mounting On interlinking block
- Max. open circuit voltage 28.8 V
- Type code CPX
- Parameterization Data format Response to short circuit/overload
- Operating error limit related to the ambient temperature range ±0.3 %
- Electrical isolation between channel and internal bus yes
- CE marking (see declaration of conformity) As per EU EMC directive
- Max. cable length 500 m
- Shock resistance Shock test with severity level 2 as per FN 942017-5 and EN 60068-2-27
- Max. input resistance 300 Ohm
- Width dimension 50 mm
- LED indicators 1 group diagnostics 4 channel status
- Intrinsic current consumption at nominal operating voltage Typ. 170 mA
- Power failure buffering 10 ms
- Relative air humidity 95 % Non-condensing
- Ambient temperature -5 °C ... 50 °C
- Sensor type 0 - 20 mA 4–20 mA with HART
- Vibration resistance Transport application test with severity level 2 as per FN 942017-4 and EN 60068-2-6
- Number of selectable analog inputs/outputs 4
- Max. load 750 Ohm
- Control elements DIL switch
- DC operating voltage range 18 V ... 30 V
- Nominal operating voltage DC 24 V
- Storage temperature -20 °C ... 70 °C
- Degree of protection Depends on manifold block
- Protocol HART
- Note on materials RoHS-compliant
Product condition
New Factory Sealed
New Factory Sealed - New condition, never used, original OEM part with original packaging and factory seal.
Related documents 8059847 Specs
Manufacturer warranty
Request a quote, and we will send you price and availability within minutes.
Select Qty:
Average response time: 11 minutes
Worldwide Shipping and Delivery
Secure Payment Processing
Warranty
Responsive Customer Support
Got Questions? We've Got Answers!
Need more details?
Feel free to chat with us
What can I help you find today?